CoolMasterNetis a unique hardware solution for seamless integration of the advanced VRF / Split Air Conditioning Systems and Home Automation / BMS Controllers. Interfacing major Home Automation controllers e.g. Control4, Crestron, AMX, RTI, Savant, Vantage and others, through CoolMasterNet’s built in RS232, RS485 and Ethernet communication ports, will provide end users with control and monitoring of Air Conditioning indoor units. Air Conditioning control will now be implemented from same Home Automation or BMS controller of which other tasks like lighting, shades, security and similar are controlled. It will also enable HVAC Service Providers to access HVAC’s most essential parameters required for diagnostic and service purposes.
Easy Integration
Home Automation integrators and HVAC installers
when integrating CoolMasterNet, will not have to worry anymore when connecting
to those advanced HVACs and hassle with their complicated communication
protocols. Integration and installation process will be straight-forward since
CoolMasterNet is a plug & play solution.
CoolRemote – HVAC Remote Access
Connecting CoolMasterNet to the
Internet as a standalone device will enable end users and HVAC Service
Providers when using smart phones, tablets or PCs to remotely access and
control those advanced VRF / Splits HVACs via CoolRemote, Cool Automation’s cloud based
solution.
Specifications
|
| Power supply | Min load* | 5V/175mA (via mini USB); 12V/120mA; 24V/70mA | | Max load** | 5V/300mA (via mini USB); 12V/200mA; 24V/120mA | | Mounting | DIN rail / wall | | Operating conditions | Ambient temperature | -10°C ~ 60°C / 14°F ~ 140°F | | Humidity | 0% ~ 96% non-condensing | | Storage conditions | Ambient temperature | -20°C ~ 70°C / -4°F ~ 158°F | | Humidity | 0 % ~ 98 % non-condensing | | Dimensions | HxWxD | 156 x 109.8 x 35.32 [mm] / 6.14 x 4.32 x 1.39 ["] | | LCD | Size / # of dots / # of colors | 2.8" / 240 x 320 / 262K | | Input | Touch panel | 8 bit encoded analog input | | Communication functions | Direct HVAC conenction | Connection to the 2 wired HVAC bus | | MODBUS (A / B) | RS-485 communication line | | Ethernet | 100Mbps | | RS-232 | DB9, 9600Bps, ASCII | | USB Host | 12Mbps | | USB Device | 12Mbps | | Maximal allowable wiring length (to BMS) over RS232 | 25 [m] / 82 [ft] | | Maximal allowable wiring length (to BMS) over RS485 | 1000 [m] / 3300 [ft] | | Maximal allowable wiring length (to router) over Ethernet | 137 [m] / 450 [ft] | | Certification | FCC, CE (EN 60335-1, EN 60335-2-40) | *One HVAC line and Ethernet are connected.
**USB host, Ethernet, HVAC lines 1-7 are connected. |
Dimensions
Combination tables
| HVAC connectivity table | | Line # | Manufacturer | Interface | Terminals | Polarity | Maximum Indoor Units
(Manufacturers
lim itation) | Maximum Outdoor Units
(Manufacturer
s Limitation) | | L1,L2 | Daikin | DIII-NET | F1 F2 | none | 64 | 10 | | Sanyo | S-NET | U1 U2 | none | 64 | 16 | | Panasonic | | U1 U2 | none | 64 | 16 | | Toshiba | TCC LINK | U1 U2 | none | 64 | 16 | | Mitsubishi Electric | M-NET | M1 M2 | none | 50 | 10 | | Hitachi | H Link, H Link 2 | 1 2 | none | 160 | 10 | L4,L5,L6,L7
* | LG | | Inter A Inter B | + - | 128 | - | | Gree | | A B | + - | 16 | 4 | | Mitsubishi Heavy Industries | SuperLink / New SuperLink | A B | + - | 128 | 10 | | Samsung | | F1 F2 / R1 R2 | + - | 64 | 10 | | Midea | | X Y E | + - GND | 64 | 16 | | Kentatsu | | X Y E | + - GND | 64 | 16 | | Trane | | X Y E | + - GND | 64 | 16 | | Chigo | | X Y E | + - GND | 64 | 16 | | Bluestar | | A B | + - | 64 | 10 | | L8 via USB Host Port | Fujitsu (external LON USB adapter
required) | LON (ANSI/CEA- 709.1-B) | X1 X2 | none | 128 | 10 | | HVAC Lines interoperability | | | L1 | L2 | L4 | L5 | L6 | L7 | L8 | | | | | L1** | | ✓ | ✓ | | ✓ | ✓ | ✓ | | | | | L2** | ✓ | | ✓ | ✓ | | ✓ | ✓ | | | | | L4 | ✓ | ✓ | | ✓ | ✓ | ✓ | ✓ | | | | | L5** | | ✓ | ✓ | | ✓ | ✓ | ✓ | | | | | L6* ** | ✓ | | ✓ | ✓ | | ✓ | ✓ | | | | | L7* | ✓ | ✓ | ✓ | ✓ | ✓ | | ✓ | | | | | L8 | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | | | | | Limitations:
Total number of supported indoors (for all HVAC Lines) can not exceed 255 units
*When DIP switches P1 and P2 are "ON", lines L6 and L7 cannot be used as separated lines. In this case the polarity on the HVAC cable connected to L7 will be automatically detected.
**Line L2 can not be connected simultaneously with line L6 and line L1 can not be connected simultaneously with
line L5. |
|