To be able to purchase this product we must hold a copy of your company F-Gas Certification on your account.
Links to accepted certification
Leader in sustainability
VRV 5: Completely new and dedicated R-32 VRV design
› Less refrigerant charge
› Higher efficiency
› Free combinations up to 28hp
Lower CO2 equivalent
Maximum flexibility out of the box:
› Install in rooms down to 7m2
› Flexible design as any other VRV system
› WebXpress selection software ensures a quick and compliant selection to the latest product standards
Specifications
|
|
|
| Capacity | Nominal Cooling kW | 14 | 22.4 | 28 | 33.5 | 40 | 45 | 50.4 | 55.9 | |
| Nominal Heating kW | 16 | 25 | 31.5 | 37.5 | 45 | 50 | 56.5 | 63 | |
|
| Dimensions | Height x Width x Depth | mm | 1685 x 930
x 765 | 1685 x 930
x 765 | 1685 x 930
x 765 | 1685 x 930
x 765 | 1685 x 930
x 765 | 1685 x 930
x 765 | 1685 x 930
x 765 | 1685 x 930
x 765 | |
| Weight kg | 203 | 284 | 307 | | Electrical Details | Power Supply Phase / Hz / V | 3 / 50 / 380~415 | | Fuse Rating amps | 20 | 20 | 25 | 32 | 32 | 40 | 40 | TBC | | Refrigerant Circuit | Refrigerant Type | R32 | | Refrigerant Charge kg | 9 | 9 | 9 | 9 | 10.6 | 10.6 | 10.6 | 10.6 | | Sound Pressure (Cooling) dBA | 56.3 | 56.3 | 58 | 60.8 | 56.1 | 60.8 | 63 | 67 | | Sound Power (Cooling) dBA | 78.3 | 78.3 | 78.8 | 82.5 | 78.7 | 83.7 | 83.4 | 87.9 | | Piping Limits | Maximum Total Length | m | 1000 | | Piping Connections - Systems | Liquid inch (mm) | 3/8 (9.5) | 3/8 (9.5) | 3/8 (9.5) | 1/2 (12.7) | 1/2 (12.7) | 1/2 (12.7) | 1/2 (12.7) | 1/2 (12.7) | | Discharge inch (mm) | 1/2 (12.7) | 5/8 (15.9) | 5/8 (15.9) | 3/4 (19.1) | 3/4 (19.1) | 3/4 (19.1) | 3/4 (19.1) | 7/8 (22.2) | | Gas inch (mm) | 5/8 (15.9) | 3/4 (19.1) | 3/4 (19.1) | 7/8 (22.2) | 7/8 (22.2) | 7/8 (22.2) | 7/8 (22.2) | 1 1/8 (28.6) | | Operation Range (Cooling) | Min / Max | °CDB | -5 / 46 | | Operation Range (Heating) | Min / Max | °CWB | -20 / 15.5 |
Specifications
|
|
|
| Capacity | Nominal Cooling | kW | 28 | 36.4 | 44.8 | 50.4 | 55.9 | |
| Nominal Heating | kW | 31.5 | 41 | 50 | 56.5 | 62.5 | | Dimensions | Height mm | 1685 | 1685 | 1685 | 1685 | 1685 | 1685 | 1685 | 1685 | 1685 | 1685 | |
| Width | mm | 930 | 930 | 930 | 930 | 930 | 930 | 930 | 930 | 930 | 930 | | Depth | mm | 765 | 765 | 765 | 765 | 765 | 765 | 765 | 765 | 765 | 765 | | Electrical Details | Power Supply | Phase / Hz / V | 3 / 50 / 380~415 | | Fuse Rating | amps | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 25 | 20 | 32 | | Refrigerant Circuit | Refrigerant Type | R32 | | Refrigerant Charge | kg | 9 | 9 | 9 | 9 | 9 | 9 | 9 | 9 | 9 | 9 | | Sound Pressure (Cooling) | | dBA | 56.3 | 56.3 | 56.3 | 56.3 | 56.3 | 56.3 | 56.3 | 58 | 56.3 | 60.8 | |
| Sound Power (Cooling) | | dBA | 78.3 | 78.3 | 78.3 | 78.3 | 78.3 | 78.3 | 78.3 | 78.8 | 78.3 | 82.5 | | Piping Limits | Maximum Length | m | 1000 | Piping Connections
- Systems | Liquid | inch (mm) | 3/8 (9.5) | 3/8 (9.5) | 3/8 (9.5) | 3/8 (9.5) | 3/8 (9.5) | 3/8 (9.5) | 3/8 (9.5) | 3/8 (9.5) | 3/8 (9.5) | 1/2 (12.7) | | Discharge | inch (mm) | 1/2 (12.7) | 1/2 (12.7) | 1/2 (12.7) | 5/8 (15.9) | 5/8 (15.9) | 5/8 (15.9) | 5/8 (15.9) | 5/8 (15.9) | 5/8 (15.9) | 3/4 (19.1) | | Gas | inch (mm) | 5/8 (15.9) | 5/8 (15.9) | 5/8 (15.9) | 3/4 (19.1) | 3/4 (19.1) | 3/4 (19.1) | 3/4 (19.1) | 3/4 (19.1) | 3/4 (19.1) | 7/8 (22.2) | | Operation Range (Cooling) | Min / Max | °CDB | -5 / 46 | | Operation Range (Heating) | Min / Max | °CWB | -20 / 15.5 |
Specifications
|
|
|
| Capacity | Nominal Cooling | kW | 61.5 | 67.4 | 73.5 | 78.5 | |
| Nominal Heating | kW | 69 | 75 | 82.5 | 87.5 | | Dimensions | Height | mm | 1685 | 1685 | 1685 | 1685 | 1685 | 1685 | 1685 | 1685 | |
| Width | mm | 930 | 930 | 930 | 930 | 930 | 930 | 930 | 930 | | Depth | mm | 765 | 765 | 765 | 765 | 765 | 765 | 765 | 765 | | Electrical Details | Power Supply | Phase / Hz / V | 3 / 50 / 380~415 | | Fuse Rating | amps | 25 | 32 | 20 | 40 | 32 | 32 | 32 | 40 | | Refrigerant Circuit | Refrigerant Type | R32 | | Refrigerant Charge | kg | 9 | 9 | 9 | 10.6 | 9 | 10.6 | 9 | 10.6 | | Sound Pressure (Cooling) dBA | 58 | 60.8 | 56.3 | 60.8 | 60.8 | 56.1 | 60.8 | 60.8 | |
| Sound Power (Cooling) dBA | 78.8 | 82.5 | 78.3 | 83.7 | 82.5 | 78.7 | 82.5 | 83.7 | | Piping Limits | Maximum Length | m | 1000 | Piping Connections
- Systems | Liquid | inch (mm) | 3/8 (9.5) | 1/2 (12.7) | 3/8 (9.5) | 1/2 (12.7) | 1/2 (12.7) | 1/2 (12.7) | 1/2 (12.7) | 1/2 (12.7) | | Discharge | inch (mm) | 5/8 (15.9) | 3/4 (19.1) | 5/8 (15.9) | 3/4 (19.1) | 3/4 (19.1) | 3/4 (19.1) | 3/4 (19.1) | 3/4 (19.1) | | Gas | inch (mm) | 3/4 (19.1) | 7/8 (22.2) | 3/4 (19.1) | 7/8 (22.2) | 7/8 (22.2) | 7/8 (22.2) | 7/8 (22.2) | 7/8 (22.2) | | Operation Range (Cooling) | Min / Max | °CDB | -5 / 46 | | Operation Range (Heating) | Min / Max | °CWB | -20 / 15.5 |
Installation
|