FXDA-A • VRV - Slim Concealed Ceiling Unit

  • Daikin
  • Slim Concealed Ceiling Unit
  • FXDA-A
  • Indoor Unit
  • Cooling 1.1kW - 7.1kW Heating 1.3W - 8.0kW
  • R32
  • VRV

F-Gas Certified

To be able to purchase this product we must hold a copy of your company F-Gas Certification on your account.

Links to accepted certification

REFCOM

F-Gas

  • Daikin

Product

Slim concealed ceiling unit

Slim design for flexible installation

Application

  • Cooling or Heating

Advantage

  • Optimised design for R-32 refrigerant
  • Compact dimensions, can easily be mounted in a ceiling void of only 240mm
  • Medium external static pressure up to 44Pa facilitates unit use with flexible ducts of varying lengths
  • Discretely concealed in the wall: only the suction and discharge grilles are visible
  • 15 class unit especially developed for small or well-insulated rooms, such as hotel bedrooms, small offices, etc.
  • Auto cleaning filter option ensures maximum efficiency, comfort and reliability by regular filter cleaning
  • Flexible installation, as the air suction direction can be altered from rear to bottom suction
  • Standard drain pump with 600mm lift increases flexibility and installation speed

Refrigerant

  • R32

Features

  • Daikin Residential Controller (optional) (optional)

    Control your indoor climate from any location via smartphone or tablet

  • Home leave operation

    Maintains the indoor temperature at your specified comfort level during absence, thus saving energy

  • Fan only

    The unit can be used as fan, blowing air without heating or cooling.

  • Auto cooling-heating changeover

    Automatically selects heating or cooling mode to achieve the set temperature.

  • Whisper quiet

    Daikin indoor units are whisper quiet. Also the outdoor units are guaranteed not to disturb the quiet of the neighbourhood.

  • Fan speed steps (3 steps + auto)

    Allows to select up to the given number of fan speed.

  • Dry programme

    Allows humidity levels to be reduced without variations in room temperature.

  • Air filter (pre filter)

    Removes airborne dust particles to ensure a steady supply of clean air.

  • Weekly timer

    Can be set to start heating or cooling anytime on a daily or weekly basis.

  • Infrared remote control (optional - must be combined with Madoka wired remote controller)

    Starts, stops and regulates the air conditioner from a distance.

  • Wired remote control (required option)

    Starts, stops and regulates the air conditioner.

  • Centralised control (optional)

    Starts, stops and regulates several air conditioners from one central point.

  • Auto-restart

    The unit restarts automatically at the original settings after power failure.

  • Self diagnosis

    Simplifies maintenance by indicating system faults or operating anomalies.

  • Multi tenant

    The indoor unit's main power supply can be turned off when leaving the hotel or office building.

  • Drain pump kit (standard)

    Facilitates condensation draining from the indoor unit.

  • Auto-cleaning filter (optional)

    The filter automatically cleans itself. Simplicity of upkeep means optimum energy efficiency and maximum comfort without the need for expensive or time-consuming maintenance.

Applicable outdoor units

  • Applicable outdoor units
    • Type RXYSA 4/5/6 AV1
    • Type RXYSA 4/5/6 AY1
    • Type REYA 8/10/12/14/16/18/20 A
    • Type REMA5-A (Multi Only)
    )

Specifications

Indoor UnitsFXDA10AFXDA15AFXDA20AFXDA25AFXDA32AFXDA40AFXDA50AFXDA63A
CapacityUK Total Cooling kW0.81.31.62.12.73.44.25.3
UK Sensible Cooling kW0.71.11.31.622.53.24
Nominal Cooling kW1.11.72.22.83.64.55.67.1
Nominal Heating kW1.31.92.53.2456.38
Air Flow RateHigh m3/sec0.0870.1080.1330.1330.1330.1750.2080.275
Nom m3/sec0.0820.1030.120.120.120.1580.1830.242
Low m3/sec0.0780.0970.1070.1070.1070.1420.1670.217
External Static PressureHigh Pa3030303030444444
Low Pa1010101010151515
Dimensions Height x Width x Depth mm200 x 750 x 620200 x 950 x 620200 x 1150
x 620
Weight kg222223232326.526.530.5
Electrical DetailsRunning Current amps0.20.30.30.30.30.40.50.5
Power Supply Phase / Hz / V1 / 50 / 230
Fuse Rating amps6
Sound LevelSound PressureHigh dBA2932333333343536
Nom dBA2831313131323334
Low dBA2627272727282930
Sound Power dBA4850515151525354
Piping ConnectionsLiquid inch (mm)1/4 (6.4)1/4 (6.4)1/4 (6.4)1/4 (6.4)1/4 (6.4)1/4 (6.4)1/4 (6.4)1/4 (6.4)
Gas inch (mm)3/8 (9.5)3/8 (9.5)3/8 (9.5)3/8 (9.5)3/8 (9.5)1/2 (12.7)1/2 (12.7)1/2 (12.7)