PRODUCTS
EShop-number
Password
Welcome to SK Sales
 

FXSA-A • VRV - Concealed Ceiling Unit (Medium Static)

F-Gas Certified

To be able to purchase this product we must hold a copy of your company F-Gas Certification on your account.

Links to accepted certification

REFCOM

F-Gas

  • Daikin

Product

Fully flat cassette

Unique design in the market that integrates fully flat into the ceiling

Application

  • Cooling or Heating

Advantage

  • Optimised design for R-32 refrigerant
  • Slimmest unit in class, only 245mm (300mm built-in height) and therefore narrow ceiling voids are no longer a challenge
  • Quiet operation: down to 25dBA sound pressure level
  • Medium external static pressure up to 150Pa facilitates using flexible ducts of varying lengths
  • Possibility to change ESP via wired remote control allows optimisation of the supply air volume
  • Discretely concealed in the wall: only the suction and discharge grilles are visible
  • 15 class unit especially developed for small or well-insulated rooms, such as hotel bedrooms, small offices, etc.
  • Optional fresh air intake
  • Flexible installation: air suction direction can be altered from rear to bottom suction and choice between free use or connection to optional suction grilles
  • Standard built-in drain pump with 625mm lift increases flexibility and installation speed

Refrigerant

  • R32

Features

  • Onecta app (optional) (optional)

    Control your indoor climate from any location via smartphone or tablet

  • Home leave operation

    Maintains the indoor temperature at your specified comfort level during absence, thus saving energy

  • Fan only

    The unit can be used as fan, blowing air without heating or cooling.

  • Auto cooling-heating changeover (heat pump)

    Automatically selects heating or cooling mode to achieve the set temperature.

  • Whisper quiet

    Daikin indoor units are whisper quiet. Also the outdoor units are guaranteed not to disturb the quiet of the neighbourhood.

  • Fan speed steps (3 steps + auto)

    Allows to select up to the given number of fan speed.

  • Dry programme

    Allows humidity levels to be reduced without variations in room temperature.

  • Air filter (pre filter)

    Removes airborne dust particles to ensure a steady supply of clean air.

  • Weekly timer

    Can be set to start heating or cooling anytime on a daily or weekly basis.

  • Infrared remote control (optional - must be combined with Madoka wired remote controller)

    Starts, stops and regulates the air conditioner from a distance.

  • Wired remote control (required option)

    Starts, stops and regulates the air conditioner.

  • Centralised control (optional)

    Starts, stops and regulates several air conditioners from one central point.

  • Auto-restart

    The unit restarts automatically at the original settings after power failure.

  • Self diagnosis

    Simplifies maintenance by indicating system faults or operating anomalies.

  • Multi tenant

    The indoor unit's main power supply can be turned off when leaving the hotel or office building.

  • Drain pump kit (standard)

    Facilitates condensation draining from the indoor unit.

Applicable outdoor units

Applicable outdoor units
  • Type RXYSA 4/5/6 AV1
  • Type RXYSA 4/5/6 AY1
  • Type REYA 8/10/12/14/16/18/20 A
  • Type REMA5-A (Multi Only)

Specifications

Indoor UnitsFXSA15AFXSA20AFXSA25AFXSA32AFXSA40AFXSA50A
CapacityUK Total CoolingkW1.21.62.12.73.34.2
UK Sensible CoolingkW11.31.62.13.73.4
Nominal CoolingkW1.72.22.83.64.55.6
Nominal HeatingkW1.92.53.2456.3
Air Flow RateHighm3/sec0.1450.150.150.1580.250.253
Nomm3/sec0.1250.1250.1250.1330.2080.208
Lowm3/sec0.1080.1080.1080.1170.1830.183
External Static PressureHighPa150150150150150150
LowPa303030303030
DimensionsHeight x Width x Depthmm245 x 550 x 800245 x 700 x 800
Weight kg23.523.523.52428.529
Electrical DetailsRunning Currentamps0.70.70.70.81.31.3
Power SupplyPhase / Hz / V1 / 50 / 230
Fuse Ratingamps6
Sound LevelSound PressureHighdBA29.53030313535
NomdBA282828293232
LowdBA252525262929
Sound PowerdBA545454556060
Piping ConnectionsLiquidinches (mm)1/4 (6.4)1/4 (6.4)1/4 (6.4)1/4 (6.4)1/4 (6.4)1/4 (6.4)
Gasinches (mm)3/8 (9.5)3/8 (9.5)3/8 (9.5)3/8 (9.5)1/2 (12.7)1/2 (12.7)

Specifications

Indoor UnitsFXSA63AFXSA80AFXSA100AFXSA125AFXSA140A
CapacityUK Total CoolingkW5.26.68.310.811.9
UK Sensible CoolingkW4.25.26.78.29.5
Nominal CoolingkW7.1911.21416
Nominal HeatingkW81012.51618
Air Flow RateHighm3/sec0.350.3830.5330.60.65
Nomm3/sec0.30.3250.450.5250.567
Lowm3/sec0.250.2670.3830.4330.467
External Static PressureHighPa150150150150150
LowPa3040405050
DimensionsHeight x Width x Depthmm245 x 1000 x 800245 x 1400 x 800245 x 1550
x 800
Weight kg35.536.5464751
Electrical DetailsRunning Currentamps1.31.51.822.7
Power SupplyPhase / Hz / V       
Fuse Ratingamps       
Sound LevelSound PressureHighdBA3335363941.5
NomdBA3032343638
LowdBA2729313334
Sound PowerdBA5961616464
Piping ConnectionsLiquidinches (mm)1/4 (6.4)1/4 (6.4)3/8 (9.5)3/8 (9.5)3/8 (9.5)
Gasinches (mm)1/2 (12.7)1/2 (12.7)5/8 (15.9)5/8 (15.9)5/8 (15.9)

Dimensions

Dimensions

Dimensions

Dimensions

Dimensions

Drawing

Installation

Mobile WebsiteAbout UsDisclaimerPrivacy policyCookie policy