600Sq Cassette - Chilled Water Fancoil
It is not possible to combine both VRV
and water based fan coils on the same
F1/F2 line
FWF Valve control requirements
2 pipe unit:
1 x valve kit EKMV3C09B
+ 1 x installation box for PCB KRP1BA101
+ 1 x valve control PCB EKRP1C11
4 pipe unit:
2 x valve kit EKMV3C09B
+ 1 x installation box for PCB KRP1BA101
+ 1 x valve control PCB EKRP1C11
Specifications
|
| Capacity | UK Total Cooling | kW | 1.2 | 1.9 | 2.5 | 3.1 | | Nominal Cooling | kW | 2 | 3.2 | 4.2 | 5.2 | | Nominal Heating | kW | 2.9 | 4 | 5.4 | 6.7 | | Dimensions | Height | mm | 260 | 260 | 260 | 260 | | Width | mm | 575 | 575 | 575 | 575 | | Depth | mm | 575 | 575 | 575 | 575 | | Weight | | kg | 19 | 19 | 19 | 19 | | Sound Power | High / Low | dBA | 44/36 | 44/36 | 50/36 | 55/42 | | Sound Pressure | High / Low | dBA | 31/26 | 31/26 | 40/26 | 45/30 | | Air Flow Rate | High | m3/min | 7.9 | 7.9 | 11.2 | 14.9 | | Water Connections | | inch | 3/4 “ BSP Female | | Electrical Data | Power Supply | | 1 ph |
Specifications
|
| Capacity | UK Total Cooling | kW | 1.1 | 1.6 | 2 | 2.5 | | Nominal Cooling | kW | 2 | 2.7 | 3.5 | 4.5 | | Nominal Heating | kW | 3.9 | 3.8 | 4.9 | 6.1 | | Dimensions | Height | mm | 260 | 260 | 260 | 260 | | Width | mm | 575 | 575 | 575 | 575 | | Depth | mm | 575 | 575 | 575 | 575 | | Weight | | kg | 19 | 20 | 20 | 20 | | Sound Power | High / Low | dBA | 44/36 | 44/36 | 50/36 | 55/42 | | Sound Pressure | High / Low | dBA | 31/26 | 31/26 | 40/26 | 45/30 | | Air Flow Rate | High | m3/min | 7.9 | 7.2 | 10.4 | 13.9 | | Water Connections | | inch | 3/4 “ BSP Female | | Electrical Data | Power Supply | | 1 ph |
|