Roundflow Cassette - Chilled Water Fancoil
It is not possible to combine both VRV
and water based fan coils on the same
F1/F2 line
FWC Valve control requirements
2 pipe unit:
1 x valve kit EKMV3C09B
+ 1 x installation box for PCB KRP1BA101
+ 1 x valve control PCB EKRP1C11
4 pipe unit:
2 x valve kit EKMV3C09B
+ 1 x installation box for PCB KRP1BA101
+ 1 x valve control PCB EKRP1C11
Specifications
|
| Capacity | UK Total Cooling | kW | 3.3 | 4.1 | 4.3 | 4.8 | | Nominal Cooling | kW | 5.8 | 6.8 | 7.7 | 8.7 | | Nominal Heating | kW | 8 | 8.9 | 10.6 | 12.1 | | Dimensions | Height | mm | 288 | 288 | 288 | 288 | | | Width | mm | 840 | 840 | 840 | 840 | | | Depth | mm | 840 | 840 | 840 | 840 | | Weight | | kg | 26 | 26 | 26 | 26 | | Sound Power | High / Low | dBA | 43/31 | 47/33 | 53/36 | 57/40 | | Sound Pressure | High / Low | dBA | 29/21 | 33/22 | 39/24 | 43/28 | | Air Flow Rate | High | m3/min | 17.7 | 20.6 | 25.4 | 30.8 | | Water Connections | | inch | 3/4 “ BSP Female | | Electrical Data | Power Supply | | 1 ph |
Specifications
|
| Capacity | UK Total Cooling | kW | 3.3 | 4 | 4.3 | 4.8 | | Nominal Cooling | kW | 5.8 | 6.6 | 7.6 | 8.7 | | Nominal Heating | kW | 7.5 | 8.4 | 9.7 | 11 | | Dimensions | Height | mm | 288 | 288 | 288 | 288 | | Width | mm | 840 | 840 | 840 | 840 | | Depth | mm | 840 | 840 | 840 | 840 | | Weight | | kg | 29 | 29 | 29 | 29 | | Sound Power | High / Low | dBA | 43/31 | 47/33 | 53/36 | 57/40 | | Sound Pressure | High / Low | dBA | 29/21 | 33/22 | 39/24 | 43/28 | | Air Flow Rate | High | m3/min | 17.1 | 19.9 | 24.6 | 29 | | Water Connections | | inch | 3/4 “ BSP Female | | Electrical Data | Power Supply | | 1 ph |
|