Net Pro Dual

Optional pcb for connection to ModBus & Dry Output Connections



Brand

  • Daikin

Application

  • For CWFC's - Connection to ModBus

Product Features


Dry Contact Outputs
Operation = On/Off
Mode = Heating/Cooling/Fan
Status = Healthy/Fault


Specifications

Modbus Register
AddressRead/Write (R/W)Name and ValuesDescription
30 001RModbus statusIndicate Modbus readiness
30 002RIndoor unit connection statusIndicate connection status
30 006RIndoor unit communication statusIndicate indoor unit communication status
31 002RIndoor unit cooling setpointIndicate minimum and maximum setpoint (cooling)
31 003RIndoor unit heating setpointIndicate minimum and maximum setpoint (heating)
32 001ROn/Off status and fan speedIndicate unit on/off status and fan speed selection
32 002ROperation modeIndicate operation mode
32 003RIndoor unit setpointIndicate unit setpoint
32 004RError codeIndicate error type
32 005RRoom temperatureIndicate room temperature measured
32 006RIndoor unit temperature sensorIndicate unit temperature sensor
32 500*RCompressor statusIndicate compressor status
42 001WOn/Off status and fan speedWrite unit On/Off status and fan speed selection
42 002WOperation modeWrite operation mode
42 003WSet temperatureWrite set temperature
* Address 32500 (compressor status) is only application for model: CKE, SQMB, BM3S, BMS/BML.