Net Pro Dual
Optional pcb for connection to ModBus & Dry Output Connections
Dry Contact OutputsOperation = On/Off
Mode = Heating/Cooling/Fan
Status = Healthy/Fault
Specifications
| Modbus Register | | Address | Read/Write (R/W) | Name and Values | Description | | 30 001 | R | Modbus status | Indicate Modbus readiness | | 30 002 | R | Indoor unit connection status | Indicate connection status | | 30 006 | R | Indoor unit communication status | Indicate indoor unit communication status | | 31 002 | R | Indoor unit cooling setpoint | Indicate minimum and maximum setpoint (cooling) | | 31 003 | R | Indoor unit heating setpoint | Indicate minimum and maximum setpoint (heating) | | 32 001 | R | On/Off status and fan speed | Indicate unit on/off status and fan speed selection | | 32 002 | R | Operation mode | Indicate operation mode | | 32 003 | R | Indoor unit setpoint | Indicate unit setpoint | | 32 004 | R | Error code | Indicate error type | | 32 005 | R | Room temperature | Indicate room temperature measured | | 32 006 | R | Indoor unit temperature sensor | Indicate unit temperature sensor | | 32 500* | R | Compressor status | Indicate compressor status | | 42 001 | W | On/Off status and fan speed | Write unit On/Off status and fan speed selection | | 42 002 | W | Operation mode | Write operation mode | | 42 003 | W | Set temperature | Write set temperature | | * Address 32500 (compressor status) is only application for model: CKE, SQMB, BM3S, BMS/BML. |
|