Indoor unit has Daikin P1/P2 & F1/F2 connectivity.
BRC1D52 - Hard wired controller (old style)
BRC1E53A - Hard wired controller
BRC1H52W - Madoka controller in White
BRC1H52S - Madoka controller in Silver
BRC1H52K - Madoka controller in Black
KRP2A52 - System adaptor PCB for remote on/off, status indication and temperature setting
RTD-Net - Modbus Interface PCB for Sky Air and VRV
RTD-20 - Energy control PCB for Sky Air and VRV
BRP4A50 - PCB Adaptor for VAM-FC series connection to 3rd party heater
KRP50-2 - PCB Adaptor for VAM-FC series connection to humidifier
Specifications
|
| Power input - 50Hz | Heat exchange mode | Nom. | Ultra high | kW | 0.097 (1) | 0.164 (1) | 0.247 (1) | 0.303 (1) | 0.416 (1) | 0.548 (1) | 0.833 (1) | | High | kW | 0.070 (1) | 0.113 (1) | 0.173 (1) | 0.212 (1) | 0.307 (1) | 0.384 (1) | 0.614 (1) | | Low | kW | 0.039 (1) | 0.054 (1) | 0.081 (1) | 0.103 (1) | 0.137 (1) | 0.191 (1) | 0.273 (1) | | Bypass mode | Nom. | Ultra high | kW | 0.085 (1) | 0.148 (1) | 0.195 (1) | 0.289 (1) | 0.417 (1) | 0.525 (1) | 0.835 (1) | | High | kW | 0.061 (1) | 0.100 (1) | 0.131 (1) | 0.194 (1) | 0.300 (1) | 0.350 (1) | 0.600 (1) | | Low | kW | 0.031 (1) | 0.045 (1) | 0.059 (1) | 0.086 (1) | 0.119 (1) | 0.156 (1) | 0.239 (1) | | Temperature exchange efficiency - 50Hz | Ultra high | % | 85.1 (1) | 80.0 (1) | 84.3 (1) | 82.5 (1) | 79.6 (1) | 83.2 (1) | 79.6 (1) | | High | % | 86.7 (1) | 82.5 (1) | 86.4 (1) | 84.2 (1) | 81.8 (1) | 84.8 (1) | 81.8 (1) | | Low | % | 90.1 (1) | 87.6 (1) | 90.5 (1) | 87.7 (1) | 86.1 (1) | 88.1 (1) | 86.1 (1) | | Enthalpy exchange efficiency - 50Hz | Cooling | Ultra high | % | 65.2 (1) | 59.2 (1) | 67.7 (1) | 62.6 (1) | 68.9 (1) | 62.6 (1) | | High | % | 67.9 (1) | 61.8 (1) | 63.8 (1) | 70.7 (1) | 66.4 (1) | 71.8 (1) | 66.4 (1) | | Low | % | 74.6 (1) | 69.5 (1) | 73.1 (1) | 76.8 (1) | 74.0 (1) | 77.5 (1) | 74.0 (1) | | Heating | Ultra high | % | 75.5 (1) | 69.0 (1) | 73.1 (1) | 72.8 (1) | 68.6 (1) | 73.8 (1) | 68.6 (1) | | High | % | 77.6 (1) | 72.2 (1) | 76.3 (1) | 75.3 (1) | 71.7 (1) | 76.1 (1) | 71.7 (1) | | Low | % | 82.0 (1) | 78.7 (1) | 82.7 (1) | 80.2 (1) | 77.9 (1) | 80.8 (1) | 77.9 (1) | | Operation mode | Heat exchange mode, bypass mode, fresh-up mode | | Heat exchange system | Air to air cross flow total heat (sensible + latent heat) exchange | | Heat exchange element | Specially processed non-flammable paper | | Dimensions | Unit | Height | mm | 305 | 368 | 731 | | Width | mm | 1113 | 1354 | | Depth | mm | 866 | 920 | 1172 | | Weight | Unit | kg | 46.5 | 61.5 | 76.5 | 160 | | Casing | Material | Galvanised steel plate | | Fan | Type | Sirocco fan | | Air flow rate - 50Hz | Heat exchan ge mode | Ultra
high | m³/h | 350 (1) | 500 (1) | 650 (1) | 800 (1) | 1,000 (1) | 1,500 (1) | 2,000 (1) | | High | m³/h | 300 (1) | 425 (1) | 550 (1) | 680 (1) | 850 (1) | 1,275 (1) | 1,700 (1) | | Low | m³/h | 200 (1) | 275 (1) | 350 (1) | 440 (1) | 550 (1) | 825 (1) | 1,100 (1) | | Bypass mode | Ultra
high | m³/h | 350 (1) | 500 (1) | 650 (1) | 800 (1) | 1,000 (1) | 1,500 (1) | 2,000 (1) | | High | m³/h | 300 (1) | 425 (1) | 550 (1) | 680 (1) | 850 (1) | 1,275 (1) | 1,700 (1) | | Low | m³/h | 200 (1) | 275 (1) | 350 (1) | 440 (1) | 550 (1) | 825 (1) | 1,100 (1) | | External static pressure - 50Hz | Ultra high | Pa | 90.0 (1) | | High | Pa | 70.0 (1) | | Low | Pa | 50.0 (1) | | Fan motor | Quantity | 2 | 4 | | Air filter | Type | Multidirectional fibrous fleeces (G3) | | Sound power level (Lwa) | dB | 51 | 54 | 58 | 61 | 62 | 65 | | Sound pressure level - 50Hz | Heat exchange mode | Ultra high | dBA | 34.5 (1) | 37.5 (1) | 39.0 (1) | 42.0 (1) | 45.0 (1) | | High | dBA | 32.0 (1) | 35.0 (1) | 36.0 (1) | 38.5 (1) | 39.0 (1) | 41.5 (1) | | Low | dBA | 29.0 (1) | 30.5 (1) | 31.0 (1) | 30.5 (1) | 32.5 (1) | 33.5 (1) | 36.0 (1) | | Bypass mode | Ultra high | dBA | 34.5 (1) | 38.0 (1) | 40.0 (1) | 42.5 (1) | 42.0 (1) | 45.0 (1) | | High | dBA | 32.0 (1) | 35.0 (1) | 34.5 (1) | 36.5 (1) | 40.0 (1) | 39.0 (1) | 41.0 (1) | | Low | dBA | 28.0 (1) | 29.5 (1) | 30.5 (1) | 32.5 (1) | 35.0 (1) | | Operation range | Min. | °CDB | -10 (2) | | Max. | °CDB | 46 | | Relative humidity | % | 80% or less | | Around unit | °CDB | 0°C~40°CDB, 80% RH or less | | On coil temperature | Cooling | Max. | °CDB | - | | Heating | Min. | °CDB | - | | Connection duct diameter | mm | 200 | 250 | 2x250 | | Insulation material | Closed cell | | Safety devices | Item | 1 | Fuse | | Control systems | Wired remote control | BRC1D52 / BRC1E53A7 / BRC1E53B7 / BRC1E53C7 | Simplified wired remote control for hotel
applications | BRC2E52C (heat recovery type) / BRC3E52C (heat pump type) | | VAM wired remote control | BRC301B61 |
Specifications
|
| General | Supplier/ Manufacturer details | Name or trademark | Daikin Europe N.V. | | Product description | Model identifier | VAM350J7V EB | VAM500J7V EB | VAM650J7V EB | VAM800J7V EB | VAM1000J7 VEB | VAM1500J7 VEB | VAM2000J7 VEB | | Type of product | Bidirectional NRVU / (3) | | Type of drive | variable speed drive | | Heat recovery system | recuperative | | Thermal efficiency | % | 77 (4) | 73 (4) | 74 (4) | 76 (4) | 73 (4) | 77 (4) | 73 (4) | | Nominal flow rate | m³/s | 0.097 | 0.139 | 0.181 | 0.222 | 0.278 | 0.417 | 0.556 | | Effective electric power input | kW | 0.096 | 0.171 | 0.203 | 0.272 | 0.409 | 0.475 | 0.817 | | Internal specific fan power | W/(m³/s) | 465 (3) | 663 (3) | 836 (3) | 757 (3) | 972 (3) | 721 (3) | 972 (3) | | Maximum external leakage | % | \<9 | \<8 | | Maximum internal leakage | % | \<8 | | Filter service warning | Displayed on controller / (5) | | Instructions for pre-/disassembly | https://www.daikin.eu/en_us/about/daikin-innovations/seasonal-efficiency.html | | Face velocity | m/s | 0.52 | 0.74 | 0.72 | 0.67 | 0.83 | 0.62 | 0.83 | | External pressure | Pa | 90 | | Internal pressure drop | Pa | 106 (3) | 155 (3) | 196 (3) | 166 (3) | 216 (3) | 158 (3) | 216 (3) | | Fan efficiency | % | 43.0 (6) | 41.9 (6) | 41.1 (6) | | | | | | | | | | | | | |
| Power supply | Name | VE | | Phase | 1~ | | Frequency | Hz | 50/60 | | Voltage | V | 220-240/220 | | Voltage range | Min. | % | -10 | | Max. | % | 10 | | Current | Minimum circuit amps (MCA) | A | 1.56 | 2.08 | 2.8 | 4.39 | 4.9 | 8.78 | 9.8 | | Maximum fuse amps (MFA) | A | 16 | | Fan motor rated output | kW | 0.08x2 | 0.106x2 | 0.210x2 | 0.210x4 | | Full load amps (FLA) | Fan motor | A | 0.62 | 0.83 | 1.12 | 1.76 | 1.96 | 1.76 | 1.96 | | Fan motor 2 | A | 0.62 | 0.83 | 1.12 | 1.76 | 1.96 | 1.76 | 1.96 | | Fan motor 3 | A | - | 1.76 | 1.96 | | Fan motor 4 | A | - | 1.76 | 1.96 |
Specifications
| Notes | | 1) Measured according to JIS B 8628 - 2003 | | (2) When the heat reclaim ventilation unit is installed upside down, the minimal allowed outdoor air temperature is 5°C. | | (3) In accordance with commission regulation (EU) No 1253/2014 | | (4) Measured according to EN308 : 1997 | | (5) Clean the filter when the filter icon appears on the controller screen. Regular filter cleaning is important for delivered air quality and for the unit's energy efficiency. | | (6) In accordance with regulation (EU) No 327/2011 | | Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | | MCA= 1,25x(FLA(FM1)+FLA(FM2)+FLA(FM3)+FLA(FM4)) | | MCA represents maximum input current. | | MFA ≤ 4 x (FLA(FM1)+FLA(FM2)+...) | | Select wire size based on the value of MCA | | Fan step 8 is nominal specs. | | The unit complies for "Code du travail" and "ERP 5e catégorie" applications according to French legislation. | | Code du travail applications are non-public buildings (example offices). | | ERP (Etablissement Recevant du Public) de 5e catégorie are smaller shops, hotels etc |
Dimensions
Dimensions
Dimensions