SK Sales Ltd uses cookies and other techniques on the website www.sksales.co.uk. When you visit the SK Sales website, we can collect and / or store information about your visit. Cookies are small information files that are stored when you visit the website on the device with which you visit our website, such as a computer, tablet, smartphone or smartwatch.
 

VAM-J • Daikin VAM-J

Brand

  • Daikin

Product

  • Total Heat Exchanger - VAM-J

Application

  • Ventilation

Advantage

PRODUCT FEATURES
  • Energy saving ventilation using indoor heating, cooling and moisture recovery
  • Ideal solution for shops, restaurants or offices requiring maximum floor space for furniture, decorations and fittings
  • Free cooling possible when outdoor temperature is below indoor temperature (eg. during nighttime)
  • Reduced energy consumption thanks to specially developed DC fan motor
  • Prevent energy losses from over-ventilation while improving indoor air quality with optional CO2 sensor
  • Can be used as stand alone or integrated in the Sky Air or VRV system
  • Optional medium and fine dust filters ePM10 70% (M6), ePM1 55% (F7), ePM1 70% (F8) to meet customer request or legislation
  • Specially developed heat exchange element with High Efficiency Paper (HEP)
  • No drain piping needed
  • Can operate in over- and under pressure
  • Total fresh air solution with optional electrical heater
  • Wide range of units: air flow rate from 350 up to 2,000 m³/h
  • Shorter installation time thanks to easy adjustment of nominal air flow rate, so less need for dampers compared with traditional installations
  • Filter change indication based on actual filter contamination

Applicable controller

Indoor unit has Daikin P1/P2 & F1/F2 connectivity.

BRC1D52 - Hard wired controller (old style)
BRC1E53A - Hard wired controller
BRC1H519W7 - Madoka controller in White
BRC1H519S7 - Madoka controller in Silver
BRC1H519K7 - Madoka controller in Black

Accessories

KRP2A52 - System adaptor PCB for remote on/off, status indication and temperature setting
RTD-Net - Modbus Interface PCB for Sky Air and VRV
RTD-20 - Energy control PCB for Sky Air and VRV
BRP4A50 - PCB Adaptor for VAM-FC series connection to 3rd party heater
KRP50-2 - PCB Adaptor for VAM-FC series connection to humidifier

Specifications

Technical SpecificationsVAM350JVAM500JVAM650JVAM800JVAM1000JVAM1500JVAM2000J
Power input - 50HzHeat exchange modeNom.Ultra highkW0.097 (1)0.164 (1)0.247 (1)0.303 (1)0.416 (1)0.548 (1)0.833 (1)
HighkW0.070 (1)0.113 (1)0.173 (1)0.212 (1)0.307 (1)0.384 (1)0.614 (1)
LowkW0.039 (1)0.054 (1)0.081 (1)0.103 (1)0.137 (1)0.191 (1)0.273 (1)
Bypass modeNom.Ultra highkW0.085 (1)0.148 (1)0.195 (1)0.289 (1)0.417 (1)0.525 (1)0.835 (1)
HighkW0.061 (1)0.100 (1)0.131 (1)0.194 (1)0.300 (1)0.350 (1)0.600 (1)
LowkW0.031 (1)0.045 (1)0.059 (1)0.086 (1)0.119 (1)0.156 (1)0.239 (1)
Temperature exchange efficiency - 50HzUltra high%85.1 (1)80.0 (1)84.3 (1)82.5 (1)79.6 (1)83.2 (1)79.6 (1)
High%86.7 (1)82.5 (1)86.4 (1)84.2 (1)81.8 (1)84.8 (1)81.8 (1)
Low%90.1 (1)87.6 (1)90.5 (1)87.7 (1)86.1 (1)88.1 (1)86.1 (1)
Enthalpy exchange efficiency - 50HzCoolingUltra high%65.2 (1)59.2 (1)67.7 (1)62.6 (1)68.9 (1)62.6 (1)
High%67.9 (1)61.8 (1)63.8 (1)70.7 (1)66.4 (1)71.8 (1)66.4 (1)
Low%74.6 (1)69.5 (1)73.1 (1)76.8 (1)74.0 (1)77.5 (1)74.0 (1)
HeatingUltra high%75.5 (1)69.0 (1)73.1 (1)72.8 (1)68.6 (1)73.8 (1)68.6 (1)
High%77.6 (1)72.2 (1)76.3 (1)75.3 (1)71.7 (1)76.1 (1)71.7 (1)
Low%82.0 (1)78.7 (1)82.7 (1)80.2 (1)77.9 (1)80.8 (1)77.9 (1)
Operation modeHeat exchange mode, bypass mode, fresh-up mode
Heat exchange systemAir to air cross flow total heat (sensible + latent heat) exchange
Heat exchange elementSpecially processed non-flammable paper
DimensionsUnitHeightmm305368731
Widthmm11131354
Depthmm8669201172
WeightUnitkg46.561.576.5160
CasingMaterialGalvanised steel plate
FanTypeSirocco fan
Air flow rate - 50HzHeat exchan ge modeUltra
high
m³/h350 (1)500 (1)650 (1)800 (1)1,000 (1)1,500 (1)2,000 (1)
Highm³/h300 (1)425 (1)550 (1)680 (1)850 (1)1,275 (1)1,700 (1)
Lowm³/h200 (1)275 (1)350 (1)440 (1)550 (1)825 (1)1,100 (1)
Bypass modeUltra
high
m³/h350 (1)500 (1)650 (1)800 (1)1,000 (1)1,500 (1)2,000 (1)
Highm³/h300 (1)425 (1)550 (1)680 (1)850 (1)1,275 (1)1,700 (1)
Lowm³/h200 (1)275 (1)350 (1)440 (1)550 (1)825 (1)1,100 (1)
External static pressure - 50HzUltra highPa90.0 (1)
HighPa70.0 (1)
LowPa50.0 (1)
Fan motorQuantity24
Air filterTypeMultidirectional fibrous fleeces (G3)
Sound power level (Lwa)dB515458616265
Sound pressure level - 50HzHeat exchange modeUltra highdBA34.5 (1)37.5 (1)39.0 (1)42.0 (1)45.0 (1)
HighdBA32.0 (1)35.0 (1)36.0 (1)38.5 (1)39.0 (1)41.5 (1)
LowdBA29.0 (1)30.5 (1)31.0 (1)30.5 (1)32.5 (1)33.5 (1)36.0 (1)
Bypass modeUltra highdBA34.5 (1)38.0 (1)40.0 (1)42.5 (1)42.0 (1)45.0 (1)
HighdBA32.0 (1)35.0 (1)34.5 (1)36.5 (1)40.0 (1)39.0 (1)41.0 (1)
LowdBA28.0 (1)29.5 (1)30.5 (1)32.5 (1)35.0 (1)
Operation rangeMin.°CDB-10 (2)
Max.°CDB46
Relative humidity%80% or less
Around unit°CDB0°C~40°CDB, 80% RH or less
On coil temperatureCoolingMax.°CDB-
HeatingMin.°CDB-
Connection duct diametermm2002502x250
Insulation materialClosed cell
Safety devicesItem1Fuse
Control systemsWired remote controlBRC1D52 / BRC1E53A7 / BRC1E53B7 / BRC1E53C7
Simplified wired remote control for hotel
applications
BRC2E52C (heat recovery type) / BRC3E52C (heat pump type)
VAM wired remote controlBRC301B61

Specifications

2-1 Technical SpecificationsVAM350JVAM500JVAM650JVAM800JVAM1000JVAM1500JVAM2000J
GeneralSupplier/ Manufacturer detailsName or trademarkDaikin Europe N.V.
Product descriptionModel identifierVAM350J7V EBVAM500J7V EBVAM650J7V EBVAM800J7V EBVAM1000J7 VEBVAM1500J7 VEBVAM2000J7 VEB
Type of productBidirectional NRVU / (3)
Type of drivevariable speed drive
Heat recovery systemrecuperative
Thermal efficiency%77 (4)73 (4)74 (4)76 (4)73 (4)77 (4)73 (4)
Nominal flow ratem³/s0.0970.1390.1810.2220.2780.4170.556
Effective electric power inputkW0.0960.1710.2030.2720.4090.4750.817
Internal specific fan powerW/(m³/s)465 (3)663 (3)836 (3)757 (3)972 (3)721 (3)972 (3)
Maximum external leakage%\<9\<8
Maximum internal leakage%\<8
Filter service warningDisplayed on controller / (5)
Instructions for pre-/disassemblyhttps://www.daikin.eu/en_us/about/daikin-innovations/seasonal-efficiency.html
Face velocitym/s0.520.740.720.670.830.620.83
External pressurePa90
Internal pressure dropPa106 (3)155 (3)196 (3)166 (3)216 (3)158 (3)216 (3)
Fan efficiency%43.0 (6)41.9 (6)41.1 (6)
           
2-2 Electrical SpecificationsVAM350JVAM500JVAM650JVAM800JVAM1000JVAM1500JVAM2000J
Power supplyNameVE
Phase1~
FrequencyHz50/60
VoltageV220-240/220
Voltage rangeMin.%-10
Max.%10
CurrentMinimum circuit amps (MCA)A1.562.082.84.394.98.789.8
Maximum fuse amps (MFA)A16
Fan motor rated outputkW0.08x20.106x20.210x20.210x4
Full load amps (FLA)Fan motorA0.620.831.121.761.961.761.96
Fan motor 2A0.620.831.121.761.961.761.96
Fan motor 3A-1.761.96
Fan motor 4A-1.761.96

Specifications

Notes
1) Measured according to JIS B 8628 - 2003
(2) When the heat reclaim ventilation unit is installed upside down, the minimal allowed outdoor air temperature is 5°C.
(3) In accordance with commission regulation (EU) No 1253/2014
(4) Measured according to EN308 : 1997
(5) Clean the filter when the filter icon appears on the controller screen. Regular filter cleaning is important for delivered air quality and for the unit's energy efficiency.
(6) In accordance with regulation (EU) No 327/2011
Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
MCA= 1,25x(FLA(FM1)+FLA(FM2)+FLA(FM3)+FLA(FM4))
MCA represents maximum input current.
MFA ≤ 4 x (FLA(FM1)+FLA(FM2)+...)
Select wire size based on the value of MCA
Fan step 8 is nominal specs.
The unit complies for "Code du travail" and "ERP 5e catégorie" applications according to French legislation.
Code du travail applications are non-public buildings (example offices).
ERP (Etablissement Recevant du Public) de 5e catégorie are smaller shops, hotels etc

Dimensions

Dimensions

Dimensions

Dimensions

Cookie policyProductsContact usJoin our teamAbout our companyPrivacy policyDisclaimer

Requesting information. Please wait a moment...