PRODUCTS
EShop-number
Password
Welcome to SK Sales
SK Sales Ltd uses cookies and other techniques on the website www.sksales.co.uk. When you visit the SK Sales website, we can collect and / or store information about your visit. Cookies are small information files that are stored when you visit the website on the device with which you visit our website, such as a computer, tablet, smartphone or smartwatch.
 

Mini Sky-Air RZAG-A • Daikin Mini Sky-Air Outdoor Unit

  • Daikin
  • Outdoor Unit
  • Daikin Mini Sky-Air
  • Air-2-Air, Heatpump, Inverter Driven
  • Cooling 3.5kW - 6.0kW Heating 4.0kW - 7.0kW
  • R32
  • Mini Sky-Air

F-Gas Certified

To be able to purchase this product we must hold a copy of your company F-Gas Certification on your account.

Links to accepted certification

REFCOM

F-Gas

Brand

  • Daikin

Product

  • Mini Sky-Air - Outdoor Unit

Function

  • Air-2-Air, Heatpump, Inverter Driven

Refrigerant

  • R32

Applicable indoor units

  • Type FTXM 35/50/60 R
  • Type FDXM 35/50/60 F9
  • Type FFA 35/50/60 A9
  • Type FNA 35/50/60 A9
  • Type FHA 35/50/60 A9
  • Type FCAG 35/50/60 A9
  • Type FBA 35/50/60 A9

Features

  • Top efficiency: - Energy labels up to A++ in both cooling and heating - compressor offers substantial efficiency improvements
  • Choosing for an R-32 product, reduces the environmental impact with 68% compared to R-410A, leads directly to lower energy consumption thanks to its high energy efficiency and has a lower refrigerant charge
  • Suits high sensible, infrastructure cooling applications
  • Replace existing systems with R-32 technology without needing to replace the piping
  • Guarantees operation in both heating and cooling mode down to -20°C
  • Maximum piping length up to 50m
  • Exclusively offered for pair applications (capacity from 35 up to 60)
  • Inverter

    Inverter compressors continuously adjust compressor speed to actual demand. Fewer power-consuming starts and stops result in decreased energy consumption (up to 30%) and more stable temperatures.

  • Auto cooling-heating changeover

    Automatically selects heating or cooling mode to achieve the set temperature.

  • Infrastructure cooling

    Remove in a reliable, efficient and flexible way the heat constantly generated by the IT and server equipment to ensure maximum uptime while offering the best return on investment.

  • Maximum pipe run = 50m on sizes 35/50/60
  • Maximum vertical rise = 30m on sizes 35/50/60
  • Swing compressor
  • DC fan motor
  • Protected valves
  • 3-Bladed rotary fan
  • Input power : 230V/1/50Hz
  • 16 Amp 300mA Earth Leakage Circuit Breaker (inverter & DC component compatible) on sizes 35/50
  • 20 Amp 300mA Earth Leakage Circuit Breaker (inverter & DC component compatible) on sizes 60
  • Operating Range (Cooling) Min -20 / Max 52 °CDB
  • Operating Range (Heating) Min -20 / Max 24 °CWB

Specifications

Outdoor unitRZAG35A50A60A
Dimensions Unit HeightxWidthxDepthmm734x870x373
Weight Unitkg52
Sound power levelCoolingdBA626364
HeatingdBA626364
Sound pressure levelCooling Nom.dBA484950
Heating Nom.dBA484950
Operation rangeCooling Ambient Min.~Max.°CDB-20 / +52
Heating Ambient Min.~Max.°CWB-20 / +24
RefrigerantType/GWPR32 / 675
Chargekg/TCO2Eq1.55/1.05
Piping connections Liquid/Gas ODinches1/4 / 3/81/4 / 1/2
 Piping lengthOU - IU Max.m50
SystemEquivalentm50
Chargelessm30
Additional refrigerant chargekg/m0.02 (for piping length exceeding 30m)
Level difference IU - OU Max.m30
Power supply Phase/Frequency/VoltageHz/VSingle / 50 / 230
Current - 50Hz Maximum fuse amps (MFA)A161620

Dimensions

Dimensions

Combination tables

Comfort cooling combination table
 FCAG-BFFA-A9FDXM-F9FBA-A9FHA-A9FTXM-RFNA-A9
capacity class35506035506035506035506035506035506071355060
RZAG35AP  P  P  P  P  P   P  
RZAG50A P  P  P  P  P  P   P 
RZAG60A  P  P  P  P  P  P   P
P = pair application

Combination tables

Infrastructure cooling combination table
 FTXM-RFHA-A9FBA-A9FDXM-F9FNA-A9FFA-A9FCAG-B
capacity class35506071355060713550607135506035506035506035506071
RZAG35A P*   P*   P*   P*  P*  P*  P*  
RZAG50A  P   P   P   P  P  P  P 
RZAG60A   P*   P*   P*            P*
P = Pair; P* = ASYCPIR asymmetric combinations piping reducer option is needed for these combinations! For more information on infrastructure cooling options refer to infrastructure cooling catalogue.

Combination tables

TypeIndoor UnitOutdoor UnitWired Remote ControllerDuty rotation(*)Capacity (kW)Seasonal efficiency**
Cooling (Nominal)Heating (Nominal)CoolingHeating
(Average climate)
Energy labelSEEREnergy labelSCOP
Slim ductFDXM35F9RZAG35ABRC1H519W/S/KYES3.54A+5.9A3.9
FDXM50F9RZAG50ABRC1H519W/S/KYES55A+5.9A3.9
FDXM60F9RZAG60ABRC1H519W/S/KYES67A+5.7A3.9
MSP ductFBA35A9RZAG35ABRC1H519W/S/KYES3.54A++6.12A+4.1
FBA50A9RZAG50ABRC1H519W/S/KYES56A+6.3A+4.1
FBA60A9RZAG60ABRC1H519W/S/KYES67A++6.15A+4.1
Fully flat cassetteFFA35A9RZAG35ABRC1H519W/S/KYES3.54A++6.4A3.8
FFA50A9RZAG50ABRC1H519W/S/KYES55.8A++6.3A+4.01
FFA60A9RZAG60ABRC1H519W/S/KYES67A+5.8A+4.04
Roundflow cassetteFCAG35ARZAG35ABRC1H519W/S/KNO3.54A++7.3A+4.3
FCAG50ARZAG50ABRC1H519W/S/KNO55.8A++6.8A+4.3
FCAG60ARZAG60ABRC1H519W/S/KNO67A++6.6A+4.25
Vertical ductFNA35A9RZAG35ABRC1H519W/S/KYES3.54A+5.9A3.9
FNA50A9RZAG50ABRC1H519W/S/KYES55A+5.9A3.9
FNA60A9RZAG60ABRC1H519W/S/KYES67A+5.7A3.9
Ceiling suspendedFHA35A9RZAG35ABRC1H519W/S/KYES3.54A++6.4A+4.1
FHA50A9RZAG50ABRC1H519W/S/KYES55.8A++6.8A+4.3
FHA60A9RZAG60ABRC1H519W/S/KYES67A++6.6A+4.2
WallFTXM35NRZAG35AWireless RCNO3.54A++7.7A++4.6
FTXM50NRZAG50AWireless RCNO56A++7.41A++4.6
FTXM60NRZAG60AWireless RCNO67A++6.9A+4.35
* Integrated duty rotation and backup functions within wired remote controller; ** According to EN14825