EPRA-DV3/W1 • Altherma 3 H HT - Outdoor Unit

F-Gas Certified

To be able to purchase this product we must hold a copy of your company F-Gas Certification on your account.

Links to accepted certification

REFCOM

F-Gas

Application

Daikin Altherma high temperature split

Features

  • By heat pump operation only, the outdoor unit delivers a leaving water temperature of 70°C at -15°C ambient temperature
  • By -15°C ambient temperature, the outdoor unit limits heating capacity loss
  • Outdoor unit extracts heat from the outdoor air, even at -28°C
  • The unit’s sleek design blends in with other household appliances.
  • Choosing for an R-32 product, reduces the environmental impact with 68% compared to R-410A, leads directly to lower energy consumption thanks to its high energy efficiency and has a 30% lower refrigerant charge
  • Guaranteed operation down to -28°C Daikin Altherma is suitable for all climates, even withstanding severe winter conditions with an operation range down to -28°C

Refrigerant

R32

Video

Technical data

Outdoor UnitsSingle PhaseThree Phase
EPRA14DV3EPRA16DV3EPRA18DV3EPRA14DW1EPRA16DW1EPRA18DW1
DescriptionClass 14Class 16Class 18Class 14Class 16Class 18
Dimensions [1]Height x Width x Depthmm990 x 1270 x 460990 x 1270 x 460990 x 1270 x 460990 x 1270 x 460990 x 1270 x 460990 x 1270 x 460
Weight kg146146146151151151
Nominal capacityHeating (a/b)kW10.17 / 10.1211.57 / 11.5112.11 / 12.0410.39 / 10.2611.82 / 11.6712.37 / 12.21
Cooling (c/d)kW10.55 / 6.9011.51 / 7.8812.46 / 8.8610.55 / 6.9011.51 / 7.8812.46 / 8.86
Seasonal space heating efficiency
(Heating Only Indoor Unit)
Space heating (Average climate) 35°CClassA+++A+++A+++A+++A+++A+++
Efficiency177177177186186186
SCOP4.514.514.514.714.714.71
Space heating (Average climate) 55°CClassA++A++A++A++A++A++
Efficiency140140140140140140
SCOP3.583.583.583.573.573.57
Seasonal space heating efficiency
(Reversible Indoor Unit)
Space heating (Average climate) 35°CClassA+++A+++A+++A+++A+++A+++
Efficiency180180180180180180
SCOP4.574.574.574.574.574.57
Space heating (Average climate) 55°CClassA++A++A++A++A++A++
Efficiency142142142142142142
SCOP3.623.623.623.633.633.63
COPHeating (e/f ) 4.86 / 3.704.86 / 3.704.86 / 3.704.50 / 3.564.50 / 3.564.50 / 3.56
EERCooling (c/d) 4.13 / 2.704.11 / 2.694.09 / 2.684.13 / 2.704.11 / 2.694.09 / 2.68
Operation rangeHeating°C-28 to +35-28 to +35-28 to +35-28 to +35-28 to +35-28 to +35
Cooling°C+10 to +43+10 to +43+10 to +43+10 to +43+10 to +43+10 to +43
Domestic Hot water°C-28 to +35-28 to +35-28 to +35-28 to +35-28 to +35-28 to +35
Sound pressure / power levelHeatingdBA43 / 5444 / 5448 / 5443 / 5443 / 5448 / 54
CoolingdBA43 / 5444 / 5448 / 5443 / 5443 / 5448 / 54
Refrigerant chargeR-32kg4.24.24.24.24.24.2
Water Connections (Diameter) inch1" (Male)1" (Male)1" (Male)1" (Male)1" (Male)1" (Male)
Piping length OU to IU [2] m10 [2]10 [2]10 [2]10 [2]10 [2]10 [2]
Power supply1-phase / 230V
/ 50Hz
1-phase / 230V
/ 50Hz
1-phase / 230V
/ 50Hz
3-phase / 400V
/ 50Hz
3-phase / 400V
/ 50Hz
3-phase / 400V
/ 50Hz
Recommended fuses A323232161616
Nominal capacity and nominal input tested according to EN 14511
Heating (a): Ambient air temperature -2°CDB and leaving water temperature 55°C (A-2/W55). Heating (b): Ambient air temperature -2°CDB and leaving water temperature 65°C (A-2/W65) Cooling (c): Ambient air temperature 35°C and leaving water temperature 18°C (A35/W18). Cooling (d): Ambient air temperature 35°C and leaving water temperature 7°C (A35/W7) Heating (e): Ambient air temperature 7°CDB and leaving water temperature 35°C (A7/W35). Heating (f ): Ambient air temperature 7°CDB and leaving water temperature 45°C (A7/W45)
Sound pressure / power measured according to EN 12102 under conditions of EN 14825
[1] Excludes aesthetic grill
[2] Spare pump capacity can be utilised to extend the interconnecting pipe length using the Daikin HSN pipe sizing tool.