Installation
The pressure switch should be installed by a competent electrician.
Ensure all power is disconnected prior to undertaking any work on the pressure switch.
The switch is normally mounted vertically with the ports facing downwards.
Applications
- Airflow proving The pressure switch can be used across a fan to provide proof of airflow.
- Dirty Filter The pressure switch can be used across a filter to provide filter dirty status.
If the switch is to be used for filter status monitoring, the pitot tube ends should be cut square. If the switch is to be
used for fan status monitoring, the ends of the pitot tube should be cut at an angle of 45°