Installation
Check that the speed controller supplied is compatible with
the fan.
Install in a dry sheltered position. Do not install in close
proximity to a heat source.
Remove the front cover of the controller by unscrewing the
fascia fixing screws. This provides access to mounting holes and electrical
terminals.
All wiring must be carried out by a suitably qualified and
competent person and comply with current applicable regulations
Installation of temperature sensors
The air temperature sensors should be mounted such that they
do not come into contact with heat sources such as direct sunlight or
heating/cooling pipework. They will then measure the actual air temperature.
Sensor cabling: Use 2 core cable which should be run so as
to avoid conduit and other cabling where pickup can result.
Operation
Switch off/on switch to on and select forward (FWD) or
reverse (REV). Generally forward is selected but reverse mode may be useful in
applications where there is a low ceiling and reverse mode will reduce chance of
papers etc been blown about.
The ADC4 has 2 modes of operation
Manual: The controller can be used to manually
control the speed of the fans using the speed adjustment dial.
Automatic: The controller can be used to
automatically adjust the speed of the fans and thus move warm air that is
rising to ceiling level back down to ground level. The fans will begin to
increase in speed (from the preset minimum) when the temperature at the high
level sensor is greater than that of the low level sensor by the amount in °C
as set by the ΔT dial.