Installation
Check that the auto changeover panel supplied is compatible with the fan motors.
Install in a dry sheltered position. Do not install in close proximity to a heat source.
All wiring must be carried out by a suitably qualified and competent person and comply with current applicable regulations.
Internal switch settings:
Switch 1 on SW3 (Auto start)
If this switch is on the unit will automatically start a fan when power is applied to the changeover panel. If this switch is off neither fan will start when power is applied to the changeover panel until the user manually starts a fan
Switch 2 on SW3 (Duty Share)
If this switch is off the automatic duty share period is 12 hours
If this switch is on the automatic duty share period is 24 hours
Operation
To start a fan that is not running press the associated button on the front panel. When a fan is running the associated run lamp should be lit.
To stop a fan that is running press the associated button on the front panel.
If the thermal contacts (TK) for the fan that is running open then that fan will stop, the associated fail lamp will light and the other fan will start.
To re-start a fan after the TK contacts have opened:
The cause of the TK contacts opening should be investigated. Once the TK contacts have closed then press the associated start button once to clear the fault and a second press will re-start the fan