ACO1TO - ADS - VFC - EN - 4.8A
Electrical Supply
ACO1TO: 230v 1Ph 50Hz fans
ACO3TO: 400v 3Ph 50Hz fans
Duty Share Method
MDS: Manual Duty Share
ADS: Automatic Duty Share
VFC: Volt Free Contacts
Fitted with normally open volt free contacts that close when either fan fails
EN: Enable Connections
Fitted with connections for external volt free contacts used to enable duty fan
x.xA: Motor Full Load Current
The full load current of each fan
Auto Changeover
The control panel will automatically changeover from the duty fan to the standby fan if the thermal overload trips or on loss of airflow detected by airflow switches (if airflow switches are fitted to the twin fan unit)
Manual duty share models
Manual duty share models are fitted with a 2-position (Fan A/Fan B) rocker switch enabling the user to manually select the duty fan. The control panel will auto changeover from the duty fan to the standby fan as described in Auto Changeover above.
Auto duty Share models
Auto duty share models are fitted with an electronic timer to provide a 12 hour cycle time for each fan. The timer has a jumper link to allow testing of the auto change over on a 1 minute test cycle for each fan. After testing the jumper link should be fitted back in the 12hr cycle time position The position of the jumper link for the test cycle and 12 hour cycle are shown below.
Volt free contacts (VFC Models)
These models are suffixed with VFC and feature 1 set of volt free contacts for a common fan fail status. The contacts are normally open and close when either fan fails.
Volt free contact enable connections (if fitted)
The control panel has the facility for the user to enable the duty fan using an external set of volt free contacts e.g. Building Management system. The duty fan will run when the contacts close.