Electronic fan speed controllers.
A
range of electronic fan speed controllers designed for speed controllable single phase motors up to 16 amps. The EFSC3,5,6 & 10 all have an illuminated on/off rocker switch and a stepless rotary knob for speed adjustment.
The FSC1.5 is a single gang surface or flush mount version of the EFSC1.5
The EFSC3-N and EFSC6-N are for fan motors where the neutral is controlled instead of the live.
INSTALLATION
1. Check that the speed controller supplied is compatible with the fan.
2. Install in a dry sheltered position. Do not install in close proximity to a heat source.
3. Remove the front cover of the controller by unscrewing the fascia fixing screws. This provides access to mounting holes
and electrical terminals.
All wiring must be carried out by a suitably qualified and competent person and comply with current applicable regulations
Operation
Switch on the controller by operating the ON/OFF switch. Rotating the control knob clockwise will increase the speed of the
fan from the pre-set minimum to full speed.
Minimum speed adjustment
On certain fans the factory set minimum pre-set may need adjusting. This can be achieved by rotating the minimum trimmer
inside the speed controller clockwise to increase the minimum level
Maximum speed adjustment
This can be achieved by rotating the maximum trimmer inside the speed controller anti-clockwise to decrease the maximum
level.
Warning
Installation of the controller and adjustment of the internal minimum and maximum trimmers should be carried out with the
electrical supply isolated
Technical Data
|
| FSC1.5 | 230v 1ph 50hz | 1.5 Amps | Surface/Flush | | EFSC1.5 | 230v 1ph 50hz | 1.5 Amps | Surface/Flush | | EFSC3P | 230v 1ph 50hz | 3 Amps | Surface/Flush | | EFSC5 | 230v 1ph 50hz | 5 Amps | Surface/Flush | | EFSC6 | 230v 1ph 50hz | 6 Amps | Surface/Flush | | EFSC10 | 230v 1ph 50hz | 10 Amps | Surface | | EFSC3N | 230v 1ph 50hz | 3 Amps | Surface/Flush | | EFSC6N | 230v 1ph 50hz | 6 Amps | Surface/Flush |
Dimensions
|
| FSC1.5 | 89 | 89 | 42 | | EFSC1.5 | 87 | 147 | 46 | | EFSC3P | 87 | 147 | 46 | | EFSC5 | 87 | 147 | 46 | | EFSC6 | 147 | 87 | 50 | | EFSC10 | 192 | 110 | 60 | | EFSC3N | 87 | 147 | 53 | | EFSC6N | 87 | 147 | 53 |
Wiring diagram 1
Notes
WIRING DIAGRAMS All wiring diagrams show connections for 3 wire fan control: U1: Controlled Live out to fan run winding U2: Neutral out to fan Aux: Maintained live out to fan capacitor
Where fan is 2 wire control (I.E. Only Live and neutral at fan terminal box omit connection Aux-CAP). If in doubt seek fan manufacturers advice
|