PRODUCTS
EShop-number
Password
Welcome to SK Sales
 

Kinetic CH • Kinetic Cooker Hood

Application

Ducting can be attached to the unit horizontally, vertically or both. Minimum internal depth of kitchen cupboard: 300mm. Horizontal and Vertical Spigots: The combination of spigot options allows installation in confined locations. If vertical and horizontal connection are required on the same outlet/inlet, additional spigots can be supplied. The condensate connection can be taken through the rear of the unit or through the side of the unit into an adjacent cupboard prior to connection into pre-installed domestic waste water system.

Composition

The telescopic hood incorporates two flat removable metal grease filters, low energy light bulbs and is available with a White or Brushed Aluminium front trim. The hood contains an integral fire damper in accordance with BRE Digest 398 and is connected to the heat recovery unit by a galvanised steel duct with access for cleaning. When the hood is opened, the heat recovery unit goes to boost speed and the summer bypass automatically opens to prevent cooking by-products entering the heat recovery cell. As an additional safety feature, the duct also contains a thermal cut-out fuse which turns off the MVHR unit in the event of excessive temperature in the airway. Cooker Hood units cannot be handed on-site and must be purchased as left hand (L) or right hand (R) models.

Specifications

  • Acoustic Top Box option for reduced in-duct noise
  • Recognised in SAP PCDB
  • Includes Cooker Hood Canopy
  • Horizontal duct option for space-saving installations
  • Fits within a 600mm wide aperture (300mm deep)
  • Integrated digital controller for simple and accurate commissioning
  • Plug and play controls; Humidistat, Wireless Remote
  • BMS connectivity
  • LS inputs (Light Switch)
  • Volt-free inputs
  • Self diagnosis for simplified fault finding
  • Adjustable delay On/delay Off timer

Selection curves

Selection curves

EPB values

SAP PCDB performance
 SAP 2009SAP 2012
Thermal efficiencySFPThermal efficiencySFP
%W/l/s%W/l/s
K+1850.72850.78
K+2850.74850.89
K+3840.83821.03
K+4830.92----

Sound values

 Sound Data (Unit only)
SpeedTest modePort Octave band, Hz, dB SWLSPL @ 3m
631252505001k2k4k8kdB(A)
20%Supply47.840.23831.128.222.123.630.921.4
Extract4738.73629.92522.423.330.820.6
Breakout43.636.237.430.927.423.324.231.418.6
40%Supply5446.650.244.544.438.328.831.931.2
Extract46.840.534.634.234.625.923.730.322.9
Breakout45.939.940.635.733.528.425.331.221.3
60%Supply58.154.557.652.251.747.638.635.838.5
Extract47.646.238.741.342.833.926.430.528.4
Breakout45.242.448.240.837.735.23031.125.2
80%Supply65.258.462.35856.552.544.141.443.6
Extract53.5534447.748.139.731.531.533.5
Breakout50.947.647.448.142.540.836.334.429.3
100%Supply66.463.266.362.561.757.45047.848.3
Extract64.255.24850.952.144.535.93537.2
Breakout555151.351.646.9464238.333.2