The FD-C Manual Operation Single Blade Fire Damper with volume control facility has been designed specifically for installations where space is at a premium. The testing and resetting of the damper and thermal fuse external of the duct allows for ease of commissioning and maintenance. NB: Access panels may be required to comply with DW145 G.3.1.5. The installation plate, with its engineered installation perforations, acts as a template to allow the marking of the fixing positions on the surface of the structure to which the plate will be affixed, allowing for a quick and efficient install.
FD-C 200 G MS
Explanation:
FD-C = Externally Resettable Circular Single Blade Damper
125 = duct diameter
Blade material
G = Galvanised Mild Steel
S = 430 Grade Stainless Steel
Accessories
MS = Single Pole Micro Switch
R-CL = Rotatable Cleat
Quick selection
|
|
|
| FD-C 100 | 100 | 220 | 1.2 | 64 | 0.0050 | | FD-C 125 | 125 | 245 | 1.6 | 73 | 0.0090 | | FD-C 150 | 150 | 270 | 2.0 | 79 | 0.0140 | | FD-C 160 | 160 | 280 | 2.1 | 81 | 0.0163 | | FD-C 200 | 200 | 320 | 2.8 | 85 | 0.0267 | | FD-C 250 | 250 | 370 | 4.0 | 88 | 0.0432 | | FD-C 300 | 300 | 420 | 5.0 | 91 | 0.0643 | | FD-C 315 | 315 | 435 | 5.1 | 91 | 00709 |
|