Light non-corroding rigid PVC for fast trouble free installation available in multiple sizes to suit installation and site requirements.
Dimensions
| Duct Type & Size | Dimensions | | Pressure (Pa) @ flow rate in l/s | | External (mm) | | | H | B | a | | 8 | 13 | 21 | 29 | 37 | 45 | 53 | 61 | | Uninsulated 110 x 54 | 60 | 115 | 35 | | 3.3 | 15.5 | 36 | 61 | 96 | 136 | 190 | 253 | | | | | | | | | | | | | | | | Duct Type & Size | Dimensions | | Pressure (Pa) @ flow rate in l/s | | External (mm) | | | H | B | a | | 8 | 13 | 21 | 29 | 37 | 45 | 53 | 61 | | Uninsulated 204 x 60 | 65 | 210 | 35 | | 1.1 | 2.5 | 5.2 | 9.8 | 16.1 | 24 | 33.6 | 45 | | Insulated 204 x 60 | 65 | 210 | 35 | | 1.1 | 2.5 | 5.2 | 9.8 | 16.1 | 24 | 33.6 | 45 | | | | | | | | | | | | | | | | Duct Type & Size | Dimensions | | Pressure (Pa) @ flow rate in l/s | | | | External (mm) | | | | | H | B | a | | 60 | 120 | 180 | | | | Uninsulated 220 x 90 | 95 | 226 | 35 | | 7 | 28 | 66 | | |
|