LF uPVC-VCD • High performance plastic

  • High performance volume control damper
  • uPVC, stainless steel and aluminium

Application

The Series LF uPVC-VCD is an exceptionally low leakage volume control damper, designed for use in highly energy efficient buildings and proven in independent tests to have a leakage over 70% below that currently required by Part L of Building Regulations.

Material

  • Extruded rigid uPVC frame and blades
  • Aluminium blade cores
  • Stainless steel seals and fixings

Composition

The plastic construction:
  • Serves to make the whole damper a thermal break, as opposed to some rival products which attempt to modify an existing metal VCD design using thermal breaks.
  • Is corrosion resistant. Perfect for coastal areas, chlorinated atmospheres such as swimming baths, and anywhere dampers may be exposed to elevated moisture levels.

As with all HVC volume control dampers, the drive system is fully protected by being enclosed within the frame. This avoids it coming into contact with dust and debris which would adversely affect performance and warrant more frequent maintenance. LF uPVC VCDs are now available with low pressure and high pressure specifications.

Order Example

LF uPVC-VCD - Model A - W500 x H500 - Belimo NM24A-SR - MH - RAL7012

Explanation
LF uPVC-VCD High performance plastic volume control damper

Connection
A Square flanged (standard)
B Square spigotted
C Circular spigotted
D Flat oval spigotted

Pressure rating
–– *nothing* Low pressure specification, (standard, for pressures up to 100 Pa including natural ventilation)
HP High pressure specification (optional, for pressures over 100 Pa)

Width x height
W Width
H Height

Control
EX Extended spindle (standard)
LQ Locking quadrant
(Actuator) State actuator code

When ordering a spring return actuator, please specify whether you require spring
open or spring close operation. If not stated, spring closed will be supplied as standard.

Prices

For price and availability please contact your local SK Sales branch

Correction factors

 Air leakage
Static pressureLow pressure specificationHigh pressure specification
Pal/sm3/hr/m2l/sm3/hr/m2
250.401.430.602.15
500.772.760.903.22
751.003.581.134.05
1001.174.191.224.37
1501.575.621.475.26
2001.967.031.736.19
2502.097.481.816.49
5003.4812.473.0711.00
7505.3219.054.2715.29
10006.9825.005.4919.66
12509.2933.276.3522.75
150011.9742.887.2225.86
175014.1850.808.2429.51
200017.7163.449.1132.64