PRODUCTS
EShop-number
Password
Welcome to SK Sales
 

DVS (RAL9010) • Steel exhaust valves

  • Cairox
  • Air valves
  • Steel
  • White, RAL 9010
  • For air exhaust
  • Extraction

Steel air exhaust valves with adjustable core and 50 mm mounting frame

Brand

  • CAIROX

Application

  • Wall or ceiling mounted valves DVS for air exhaust inside buildings.

Material

  • Steel

Colour

  • Standard colour white, RAL 9010

Composition

  • Pressed steel valve with adjustable core, supplied with galvanized steel mounting frame

Mounting

  • Fixing in the mounting frame

Order Example

  • DVS, 100


Explanation

DVS = Type valve (incl. mounting frame and clamping ring)

100 = Connection diameter

Quick selection

Qv

Ø

80

100125150160200

r

-15

0

+12

-10

0

+10

-17

0

+9

-15

0

+10

-20

0

+5

-25

0

+20

15Ps

100

  

90

  

30

           
Lw

31

  

19

  

<15

           
25Ps 

<20

  

<20

 

80

  

20

  

30

  

<20

  
Lw 

<15

  

<15

 

23

  

<10

  

<15

  

15

  
50Ps 

45

  

40

<20

 

<20

 

65

  

125

  

90

  
Lw 

29

  

24

<15

 

<15

 

26

  

31

  

25

  

100

Ps  

55

  

55

 35

<20

 

22

  

20

    
Lw  

34

  

28

 

20

<15

 

<15

  

<15

    

200

Ps        

70

 

110

44

 

75

45

 

37

 
Lw        

34

 

39

28

 

34

29

 

23

 

300

Ps           

90

  

105

 

85

23

Lw           

39

  

40

 

35

15

400

Ps                 

40

Lw

                 

27

Symbols and specifications

  • Qv = Air volume in m³/h
  • Ps = Static pressure loss in Pa
  • Lw = Acoustic power in dB(A), based upon measured Lp acoustic pressures increased by 4 dB(A) room attenuation
  • r = Gap between the central core and the valve body

Selection Graph

Symbols

  • Qv = Air volume in l/s
  • Pt = Total pressure loss in Pa
  • Lp10A = Acoustic pressure in dB(A) with 4dB room attenuation (10m²sab)
  • r = Gap between the central core and the valve body

Correction factor Koct (dB)

DVSf[Hz]
1252505001000200040008000
801-210-3-10-22
1005-2-3-30-8-20
125-600-30-13-25
150-6-5-40-1-13-28
1601-1-31-2-15-32
20031-11-4-12-25
Tol.±3222223

Symbols and specifications

  • To Obtain the sound power level Lw octave by octave band the value Koct need to be added to the graph value Lp10A acoording the formula = Lw oct =Lp10A + Koct
  • The correction factors Koct given are the average values ​​over the range of DVS
  • f [Hz] = Octave band in Hertz
  • Koct = Correction factor in dB per octave band

Sound attenuation DL

DVSr [mm]f [Hz]
631252505001000200040008000
100-102319141211101314
023161187698
1023161175478
125-1720191310771114
018161064458
91916963357
150-1521141186688
02013964476
101614943277
160-1518131176688
-1018131065577
01713954366
200-151712876789
-51711765668
01711755667
Tol.±632222223

Symbols and specifications

  • The above table shows the attenuation DL from duct to room, including end reflection of a flexible connection by ceiling installation.
  • r = setting of the central cone in mm

Dimensions

ØD [mm]ØN1 [mm]h [mm]ØN2 [mm]L [mm]
DVS 100991254513728
DVS 1251241504516429
DVS 1501491754520230
DVS 1601591854521231
DVS 2001992254524833
Mobile WebsiteAbout UsDisclaimerPrivacy policyCookie policy