Steel air supply valves with adjustable core and 50 mm mounting frame
Explanation
P-DVS = Type valve (incl. mountingframe and clamping ring)
100 = Connection diameter
Quick selection
|
r | -3 | 0 | +9 | -3 | 0 | +10 | -7 | 0 | +15 | -5 | 0 | +15 | -10 | 0 | +15 | -3 | 0 | +20 | 15 | Ps | 91 | | | 90 | | | | | | | | | | | | | | | Lw | 32 | | | 30 | | | | | | | | | | | | | | | 25 | Ps | | 41 | | | 39 | | <20 | | | | | | | | | | | | Lw | | 23 | | | 22 | | <15 | | | | | | | | | | | | 50 | Ps | | | 27 | | | <20 | 75 | 20 | | 30 | | | 85 | | | 100 | | | Lw | | | 26 | | | <15 | 34 | <20 | | 24 | | | 41 | | | 33 | | | 100 | Ps | | | | | | 52 | | 80 | <20 | | 50 | | | 37 | | | 80 | | Lw | | | | | | 38 | | 37 | <15 | | 28 | | | 24 | | | 34 | | 200 | Ps | | | | | | | | | 55 | | | 30 | | | 25 | | | <20 | Lw | | | | | | | | | 39 | | | 27 | | | 23 | | | <10 | 300 | Ps | | | | | | | | | | | | 70 | | | 55 | | | 25 | Lw | | | | | | | | | | | | 41 | | | 37 | | | 22 | 400 | Ps | | | | | | | | | | | | | | | | | | 45 | Lw | | | | | | | | | | | | | | | | | | 31 |
Symbols and specifications
- Qv = Air volume in m³/h
- Ps = Static pressure loss in Pa
- Lth 0.20 = Horizontal throw at end velocity of 0.20 m/s in m
- Lw = Acoustic power in dB(A), based upon measured Lp acoustic pressures increased by 4 dB(A) room attenuation
- r = Gap between the central core and the valve body
Selection Graph
Symbols
- Qv = Air volume in l/s
- Pt = Total pressure loss in Pa
- l 0.2 = Horizontal throw at end velocity of 0.20 m/s in m
- Lp = Acoustic pressure in dB(A
- r = 10mm, 30mm = Gap between the central core and the valve body
Correction factor Koct (dB)
|
|
80 | 2 | 2 | 1 | 0 | -3 | -9 | -17 | 100 | 7 | 3 | 2 | -2 | -6 | -14 | -30 | 125 | 3 | 6 | 4 | -3 | -11 | -21 | -37 | 150 | 7 | 5 | 3 | -2 | -10 | -20 | -34 | 160 | 6 | 7 | 3 | -3 | -11 | -27 | -34 | 200 | 7 | 6 | 3 | -2 | -10 | -25 | -34 | Tol.± | 3 | 2 | 2 | 2 | 2 | 2 | 3 |
Symbols and specifications
- To Obtain the sound power level Lw octave by octave band the value Koct need to be added to the graph value Lp10A acoording the formula = Lw oct =Lp10A + Koct
- The correction factors Koct given are the average values over the range of DVS
- f [Hz] = Octave band in Hertz
- Koct = Correction factor in dB per octave band
Sound attenuation DL
|
|
80 | -3 | 24 | 21 | 16 | 12 | 9 | 7 | 5 | 5 | 3 | 24 | 19 | 13 | 10 | 7 | 4 | 4 | 4 | 9 | 24 | 19 | 13 | 9 | 6 | 3 | 3 | 4 | 100 | -3 | 24 | 19 | 13 | 10 | 9 | 9 | 11 | 9 | 6 | 23 | 16 | 11 | 7 | 6 | 5 | 6 | 6 | 10 | 23 | 17 | 11 | 7 | 5 | 5 | 5 | 6 | 125 | -7 | 19 | 16 | 11 | 7 | 4 | 4 | 5 | 6 | 0 | 18 | 16 | 10 | 6 | 4 | 3 | 4 | 6 | 15 | 19 | 15 | 9 | 5 | 3 | 2 | 3 | 4 | 150 | -5 | 20 | 13 | 10 | 7 | 5 | 4 | 5 | 5 | 3 | 19 | 12 | 9 | 5 | 4 | 3 | 4 | 4 | 15 | 19 | 12 | 8 | 4 | 3 | 2 | 4 | 3 | 160 | -5 | 18 | 13 | 10 | 6 | 5 | 5 | 5 | 6 | 5 | 17 | 12 | 9 | 5 | 4 | 3 | 4 | 4 | 10 | 17 | 12 | 8 | 5 | 4 | 3 | 4 | 3 | 200 | 3 | 17 | 12 | 8 | 7 | 7 | 5 | 7 | 6 | 6 | 17 | 12 | 7 | 6 | 6 | 5 | 7 | 5 | 12 | 17 | 11 | 6 | 5 | 5 | 4 | 6 | 5 | Tol.± | 6 | 3 | 2 | 2 | 2 | 2 | 2 | 2 | 3 |
Symbols and specifications
- The above table shows the attenuation DL from duct to room, including end reflection of a flexible connection by ceiling installation.
- r = setting of the central cone in mm
Dimensions
|
P-DVS 080 | 79 | 105 | 45 | 115 | 27 | P-DVS 100 | 99 | 125 | 45 | 137 | 28 | P-DVS 125 | 124 | 150 | 45 | 164 | 29 | P-DVS 150 | 149 | 175 | 45 | 202 | 30 | P-DVS 160 | 159 | 185 | 45 | 212 | 31 | P-DVS 200 | 199 | 225 | 45 | 248 | 33 |
|