PRC+RC • Circular ceiling diffuser

  • Cairox
  • Circular diffuser
  • Steel
  • White, RAL 9016
  • Volume Control Damper

Circular ceiling diffuser with fixed diffusion rings

Application

  • For air supply in ventilation and air conditioning systems.

Material

  • Aluminium

Colour

  • White, RAL 9016

Composition

  • Fixed diffusion rings

Mounting

  • Fixing directly on the collar
  • Fixing with central screw

Order Example

  • PRC+RC 200


Explanation

PRC+RC = Diffuser type

200 = Diffuser size (Ø diffuser neck connection)


Dimensions

PRC+RC
ØA [mm]
ØB [mm]
ØC [mm]
150
250159210
200
300199260
250
342249300
315
398314350

Quick selection

PRC+RC150200250315
QAk0.0090.0140.020.028
100Vk3.2   
X0,250.7   
Ps4   
Lw(A)<20   
150Vk4.83  
X0,251.10.9  
Ps94  
Lw(A)<20<20  
200Vk6.442.8 
X0,251.51.21 
Ps1663 
Lw(A)29<20<20 
300Vk9.664.13
X0,252.21.81.51.3
Ps371574
Lw(A)4329<20<20
400Vk12.885.54
X0,2532.421.7
Ps6526126
Lw(A)533927 
500Vk 106.95
X0,25 32.42.1
Ps 401910
Lw(A) 473525
600Vk  8.36
X0,25  2.92.5
Ps  2714
Lw(A)  4132
700Vk  9.67
X0,25  3.42.9
Ps  3720
Lw(A)  4737
800Vk   8
X0,25   3.3
Ps   26
Lw(A)   42
900Vk   9
X0,25   3.8
Ps   33
Lw(A)   46
1000Vk    
X0,25    
Ps    
Lw(A)    

Symbols and specifications

  • Q = Air Volume in m³/h
  • Ak = Effective surface (free area) in m²
  • Vk = Average effective velocity through the grill in m/s
  • X0.25 = Throw length in m at an endvelocity Vt of 0,25m/s
  • Ps = Static pressure loss given in Pa
  • Lw(A) = Acoustic power in dB(A)


  • The throw X0.25 is given at an end velocity of 0.25m/s for a smooth ceiling without any obstacles.
  • The values are given for isothermal supply air. Throw distances for cooling conditions at -11K can be calculated by deviding the X0.25 values with factor 1.1. For heating purposes at Dt of +11K a multiplier of 1.1 should be applied to the given X0.25 value.
  • In order to achieve a high comfort level, selections can be made according to the maximal velocity at the occupied zone Vz. These values are given at distances between diffusers B and installation heights H. Velocities Vz lower than, or equal to 0,25m/s at the occupied zone are advised.
  • The pressure losses Ps are given for grilles without damper of with fully opened damper.
  • The acoustic power Lw(A) are given for grilles without damper of with fully opened damper without room attenuation. Acoustic powers below 20dB(A) are mentioned as "<20" in the tables.
  • For all special requirements, please contact our engineering office.